Local Controls
Maintenance
This menu includes all diagnostic and historic data which can assist the operator if failures
occur or during maintenance operations. The Maintenance menu also includes the
“Set password” routine.
List of routines:
Set-up Mode
- set new password
- clear alarm log
- set torque prole reference
- set torque curve reference
- clear recent data log
- set maintenance date
- set data logger
View Mode
- alarm log
- torque prole
- torque curve
- operation log
- maintenance date
- data logger
The parameters appear on the alphanumeric display in the same order in both view and
set-up mode. At the end of each routine, the program will automatically return to the
beginning of the routine and the operator can choose to either re-enter (by pressing YES)
or move on to a next routine (by pressing NO).
6.3 Entering the View Mode
The existing actuator conguration should be checked before commissioning.
The parameters are congured at the factory according to standard settings, or to
customer requirements. No password is required to access view mode, but no change of
parameters can be made.
Ensure that mains power is supplied.
Move the 3-position selector to OFF and then simultaneously press OPEN/YES
and STOP.
The display shows the present language. Press YES to conrm or NO to scroll
through the list of available languages. Press YES to select a new language
Press YES to conrm.
Press NO to scroll through the list of available menus (actuator set-up, nameplate,
valve data, maintenance) and then press YES to select the desired menu.
Press NO to scroll through the list of available routines and press YES to select
the routine where the parameter to be changed is located.
Press NO to scroll through the list of parameters and press YES to view the value.