Section 9: Set-Up Routines
Set-Up Routines
Conguration procedure
• Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and then enter the password according to the instructions
(see “Entering the set-up mode”). When the message displayed is “SET-UP MODE
OK?” press YES. Press YES to select the "Actuator Setup" menu, press NO to scroll
through the list of available routines, and then press YES to select "2-Speed
Timer".
• Press YES to change the close direction parameters, press NO, and then press YES
to change only the open direction parameters.
Closing direction
• Press YES if the status is OK, or NO to change. Press YES to conrm (status = On,
enables 2-speed timer operation in closing direction; status = Off, disables timer
operation in closing direction).
• Press YES if the position value where pulsing control starts is correct; if not, press
NO to scroll through the list of available values. Press YES when the value is correct.
• Press YES if the position value where pulsing control stops is correct; if not, press
NO to scroll through the list of available values. Press YES when the value is correct.
• Press YES if the value of the ON time of pulsing control is correct; if not, press NO
to scroll through the list of available values. Press YES when the value is correct.
• Press YES if the value of the OFF time of pulsing control is correct; if not, press NO
to scroll through the list of available values. Press YES when the value is correct.
Opening direction
• Press YES if the status is OK, or NO to change. Press YES to conrm (status = On
enables 2-speed timer operation in opening direction; status = Off, disables timer
operation in opening direction).
• Press YES if the position value where pulsing control starts is correct; if not, press
NO to scroll through the list of available values. Press YES when the value is correct.
• Press YES if the position value where pulsing control stops is correct; if not, press
NO to scroll through the list of available values. Press YES when the value is correct.
• Press YES if the value of the ON time of pulsing control is correct; if not, press NO
to scroll through the list of available values. Press YES when the value is correct.
• Press YES if the value of the OFF time of pulsing control is correct; if not, press NO
to scroll through the list of available values. Press YES when the value is correct.
9.1.12 BUS (or FDI Control)
This routine is only available if a eldbus interface card is present. The routine allows
setting of the most important parameters (node address, termination, etc.) necessary to
connect the actuator to a eldbus. If the ICON3000 was set to work with a eldbus but
the relevant eldbus card is not present, a hardware alarm will be generated. Different
interfaces are available to connect the ICON3000 to different types of eldbus. If the bus
interface is LonWorks, the routine “BUS” changes to “FDI control”. Refer to the specic
manuals for instructions and setting of the above modules.