December 2019
59
Installation, Operation and Maintenance Manual
VCIOM-08500-EN
Section 9: Set-Up Routines
Set-Up Routines
Auxiliary output relays
For status indication or diagnostic purposes, 8 voltage-free contacts of 8 relays are available
to be congured individually to switch upon occurrence of the following conditions:
Status
open limit
closed limit
position >= xx %
position <= xx %
closing
opening
motor running
blinker
mid-travel position
local selected
remote selected
local stop active
ESD signal on
manual operation
interlock PST-icon
heater-only AS8
Alarm
motor over-temperature
over-torque
over-torque in OP
over-torque in CL
valve jammed
valve jammed in OP
valve jammed in CL
low lithium battery (if present)
mid travel alarm in CL/OP
mains-only AS8
Warning
warnings
PST failed (i.e. Partial Stroke Test failure)
The contacts may be congured to make or break on condition. The options “EFS in
manual”, “EFS mid-travel” and “PST failed” also appear in the menu, but are not available
on the ICON3000.