March 2021
Installation, Operation and Maintenance Manual
MDE 254 Rev. 1
HART Command Set38
Section 8: HART Command Set
8.2.10 Command #109: Burst Mode Control
This command is used to enter and exit the Burst Mode on the field device.
Table 106. Request Data Bytes
Table 107. Response Data Bytes
Byte Format Description
0 Unsigned-8 Burst Mode Control Code (see Section 8.4, Table 133)
1 Unsigned-8 Burst Message
Byte Format Description
0 Unsigned-8 Burst Mode Control Code (see Section 8.4, Table 133)
1 Unsigned-8 Burst Message
Code Class Description
0 Success No Command-Specific Errors
1 Undefined
2 Error Invalid Selection
3 - 4 Undefined
5 Error Too Few Data Bytes Received
6 Error Device-Specific Command Error
7 Error In Write Protect Mode
8 Warning Update Period Increased
9 Error Insufficient bandwidth
10 - 15 Undefined
16 Error Access Restricted
17 - 31 Undefined
32 Error Busy (Delayed Response could not be initiated)
33 Error Delayed Response Initiated
34 Error Delayed Response Running
35 Error Delayed Response Dead
36 Error Delayed Response Conflict
37 - 127 Undefined
Table 108. Command-Specific Response Codes
8.2.11 Catch Device Variable
This device does not support Catch Device Variable.