BIFFI ICON3000 - Device Variable 19: 2 SP - Open Start Position; Device Variable 20: 2 SP - Open Stop Position; Device Variable 21: 2 SP - Open ON Time; Device Variable 22: 2 SP - Open OFF Time

BIFFI ICON3000
74 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
March 2021
Installation, Operation and Maintenance Manual
MDE 254 Rev. 1
Device Variables54
Section 9: Device Variables
Value Description
0 Off: Function Disabled
1 Close
2 Open
3 Stay-Put
4 Go to Position
Value Description
0 AC 3 Ph
1 AC 1 Ph
2 DC
9.27 Device Variable 24: Fail Safe Delay
This variable indicates the delay time before running the fail safe action (Device Variable 30).
9.28 Device Variable 25: Fail Safe Position
This variable indicates the position to drive the actuator when the fail safe action (Device Variable 30)
is programmed to “Go to position”.
9.29 Device Variable 26: Power Supply Type
This variable indicates the actuator power supply type. This is an enumerated variable, it’s not
possible to write this data. The possible values are:
Table 146.
9.24 Device Variable 21: 2SP – Open Direction
ON Time
This variable indicates the ON time of motor in 2 Speed Timer operation in open direction.
9.25 Device Variable 22: 2SP – Open Direction
OFF Time
This variable indicates the OFF time of motor in 2 Speed Timer operation in open direction.
9.26 Device Variable 23: Fail Safe Action
This variable indicates the action to run in case of 4 - 20 mA input signal failure. This in an enumerated
variable, the possible values are:
Table 145.