March 2021
Installation, Operation and Maintenance Manual
MDE 254 Rev. 1
Conguration of ICON300058
Section 11: Configuration of ICON3000
Configuration procedure:
Move the local selector to OFF and then press simultaneously OPEN and STOP. Select the
language and then enter the password according to the instructions “entering the set-up
mode”. When the message of display is “SET-UP MODE OK?” press YES. Press YES to select
actuator set-up menu, press NO to scroll the list of available routines and then press YES to
select the routine BUS.
Press NO if the conditions DIN1 is correct. Press YES to change. Press NO to change
condition to switch, press TES to select.
Repeat the previous procedure for DIN 2 up to DIN 6.
Press YES if the configured value of the polling node address (ADDRESS) is correct (from 1
to 63), or press NO to change, then press YES.
Press YES if the configured value of the MODE (Loop current enable, loop current disable,
multidrop) is correct, or press NO to change, then press YES.
Press YES to confirm the configured Device number.
View procedure:
Move the local selector to OFF and then press simultaneously OPEN and STOP. Select the
language and then enter the password according to the instructions “entering the view
mode”. When the message of display is “VIEW MODE OK?” press YES. Press YES to select
actuator set-up menu, press NO to scroll the list of available routines and then press YES to
select BUS.
Press YES to scroll the list of BUS parameters.
11.2 Positioner Function
The function is available only on the modulating actuators. The value 0.0 of position request,
received from bus, corresponds to close request and the value 100.0 corresponds to open request.
The ICON3000 compares the present position % of the actuator with the position request % received
from the bus (analog 4 - 20 mA HART current loop or digital HART signal), and if the difference is
greater than the dead band, the actuator is driven to reach the new requested position.
The following options can be configured via either bus or local operator interface:
Dead band: Configurable from 0.1% to 25.5% of the maximum position error (difference
among position request % and present position %). The configured value should be great
enough to avoid “hunting” effect of the actuator.
Motion inhibit time: It allows adjusting the length of the delay time between two cycles
of the motor. It can be configured from 1 to 255 seconds and allows to set the maximum
number of start / hour of electrical motor.
Configuration procedure:
Move the local selector to OFF and then press simultaneously OPEN and STOP. Select the
language and then enter the password according to the instructions “entering the set-up
mode”. When the message of display is “SET-UP MODE OK?” press YES. Press YES to select
actuator set-up menu, press NO to scroll the list of available routines and then press YES to
select POSITIONER.
Press YES if the configured value of the Dead Band is correct (from 0.1 to 25.5% of position
error), or press NO to change, then press YES.
Press YES if the configured value of the Motion Inhibit Time is correct (from 1 to 255 seconds),
or press NO to change, then press YES.

Table of Contents

Other manuals for BIFFI ICON3000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the BIFFI ICON3000 and is the answer not in the manual?

BIFFI ICON3000 Specifications

General IconGeneral
BrandBIFFI
ModelICON3000
CategoryControl Unit
LanguageEnglish

Related product manuals