March 2021
Installation, Operation and Maintenance Manual
MDE 254 Rev. 1
HART Command Set36
Section 8: HART Command Set
8.2.8 Command #107: Write Burst Device Variables
This command selects the Device Variables that will be used by a bursting device to be return by a
Command 9 in Burst Mode.
If the trigger mode isn’t Continuous in Command 104 and the trigger source’s Device Variable
Classification does not match the new Slot 0 Device Variable, the new values will be accepted
and Response Code “Burst Condition Conflict” will be returned. The field device corrects the
classification, unit codes, reset to Trigger Mode Continuous and publish continuously at the Update
Period until it receives another Command 104.
Table 99. Request Data Bytes
Table 100. Response Data Bytes
Byte Format Description
0 Unsigned-8 Device Variable Code assigned to Slot 0 (see Section 9.1)
1 Unsigned-8 Device Variable Code assigned to Slot 1 (see Section 9.1)
2 Unsigned-8 Device Variable Code assigned to Slot 2 (see Section 9.1)
3 Unsigned-8 Device Variable Code assigned to Slot 3 (see Section 9.1)
4 Unsigned-8 Device Variable Code assigned to Slot 4 (see Section 9.1)
5 Unsigned-8 Device Variable Code assigned to Slot 5 (see Section 9.1)
6 Unsigned-8 Device Variable Code assigned to Slot 6 (see Section 9.1)
7 Unsigned-8 Device Variable Code assigned to Slot 7 (see Section 9.1)
8 Unsigned-8 Burst Message
Byte Format Description
0 Unsigned-8 Device Variable Code assigned to Slot 0 (see Section 9.1)
1 Unsigned-8 Device Variable Code assigned to Slot 1 (see Section 9.1)
2 Unsigned-8 Device Variable Code assigned to Slot 2 (see Section 9.1)
3 Unsigned-8 Device Variable Code assigned to Slot 3 (see Section 9.1)
4 Unsigned-8 Device Variable Code assigned to Slot 4 (see Section 9.1)
5 Unsigned-8 Device Variable Code assigned to Slot 5 (see Section 9.1)
6 Unsigned-8 Device Variable Code assigned to Slot 6 (see Section 9.1)
7 Unsigned-8 Device Variable Code assigned to Slot 7 (see Section 9.1)
8 Unsigned-8 Burst Message
Code Class Description
0 Success No Command-Specific Errors
1 Undefined
2 Error Invalid Selection
3 - 4 Undefined
5 Error Too Few Data Bytes Received
6 Error Device-Specific Command Error
7 Error In Write Protect Mode
8 Warning Burst Condition Conflict
9 Error Invalid Burst Message
10 - 127 Undefined
Table 101. Command-Specific Response Codes