EasyManua.ls Logo

Binder MKF - Set-point Entry via Setpoints Menu

Default Icon
177 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MKF / MKFT (E5) 06/2020 page 53/176
Humidity
Setting range 0% r.h. up to 100 % r.h.
Control ranges
10 % r.h. up to 98 % r.h.
5 % r.h. up to 98% r.h. with optional compressed air dryer
Fan speed (MKF 56)
Setting range 30 % up to 100 %
See temperature / humidity diagrams in chap. 17
MKF 56: Reduce the fan speed only if required, because the spatial temperature distribution
of will also be reduced.
Technical data refers to 100% fan speed.
For the control range of temperature and relative humidity, see the temperature / humidity diagram (chap.
17).
With set-point type “Limit”, adapt the safety controller (chap. 12.2) or the over/under tempera-
ture safety device class 2 (option, chap. 12.3) always when you changed the temperature set-
point. Set the safety controller set-point or the set-point of the over/under temperature safety
device class 2 (option) by approx. 2 °C to 5 °C above the controller temperature set-point.
Recommended setting: Set-point type “Offsetwith safety controller set-point 2 °C.
7.1 Set-point entry through the “Setpoints” menu
Press the Setpoint setting icon to access the “Setpoint” setting menu from Normal display.
“Setpoints” menu (example: MKF 56).
Select “Fixed value operation setpoints” to access the
individual parameters.
Select the field Temperatureand enter the desired temperature setpoint.
Setting range: MKF: -50 °C up to 180 °C, MKFT: -80 °C up to 180 °C.
Confirm entry with Confirm icon.
Select the field Humidityand enter the desired humidity setpoint.
Setting range: 0% r.h. up to 100% r.h. Confirm entry with Confirm icon.
MKF 56: Select the field Fanand enter the desired fan speed setpoint.
Setting range: 30% up to 100% fan speed. Confirm entry with Confirm icon.

Table of Contents

Related product manuals