MARK V
1-1
OVEN SPECIFICATIONS
ELECTRICAL SPECIFICATIONS
Installations within the U.S. and Canada
Single phase models require a 60 Hz,
208/240VAC, 3 wire service consisting of L1, L2
and ground. Three phase models require a 60 Hz,
208/240/440/480, 4 wire service consisting of L1,
L2, L3 and ground. Wiring from the power source
to any of the single phase units must be a minimum
of #6 AWG copper stranded wire. Wiring from the
power source to the 208/240 three phase units
must be a minimum of #8 AWG copper stranded
wire. Wiring from the power source to the 440/480
three phase units must be a minimum of #12 AWG
copper stranded wire.
General Export Installations
Single phase models require a 50 Hz,
220/240VAC, 3 wire service consisting of L1, L2
and ground. Three phase models require a 50 Hz,
415/240 or 380/220 VAC, 5 wire service consisting
of L1, L2, L3, neutral and ground. Use 90_C wire
and size according to local codes.
CE approved installations
Single phase models require a 50 Hz, 230VAC 3
wire service consisting of L1, neutral and ground.
Three phase models require a 50 Hz, 400/230VAC,
5 wire service consisting of L1, L2, L3, neutral and
ground. Use 90_C wire and size according to local
codes.
ELECTRICAL SPECIFICATIONS (per section)
KW Hz Volts Phase
Amps
Electrical Connection
(ii i )
L1 L2 L3 N
(minimum size)
U.S. and Canadian installations
11.0 60 208 1 51 - 51 - 6 AWG
11.0 60 208 3 31 29 29 - 8 AWG
11.0 60 220Ć240 1 44 - 44 - 6 AWG
11.0 60 220Ć240 3 26 24 24 - 8 AWG
11.0 60 440 3 15 14 14 - 12 AWG
11.0 60 480 3 14 13 13 - 12 AWG
General Export installations
11.0 50 208 3 18 18 18 4 Size per local code
11.0 50 220Ć240 1 48 - - 48 Size per local code
11.0 50 220/380 3 18 16 16 2 Size per local code
11.0 50 240/415 3 18 14 14 4 Size per local code
11.0 50 230/400 3 18 15 15 3 Size per local code
CE installations
11.0 50 400 3N 18 15 15 3 Size per local code