24 en | Installing Access Modular Controller 2
2022-11 | V04 |
Guide d'installation
Bosch Security Systems B.V.
Notice!
If using an Ethernet connection, set switch 1 and 5 to ON (= delivery status).
Figure4.14: Location of the selector for host settings and delivery status
Address
DIP switches
1 2 3 4
none OFF OFF OFF OFF
1 ON OFF OFF OFF
2 OFF ON OFF OFF
3 ON ON OFF OFF
4 OFF OFF ON OFF
5 ON OFF ON OFF
6 OFF ON ON OFF
7 ON ON ON OFF
8 OFF OFF OFF ON
Table4.1: Setting the address via the DIP switch
Mode
DIP switches
5 6
ON SDEB PI
OFF BPA RS-485
Table4.2: Protocol and connection settings
Host settings
Instructions for DIP switch 5
Set SDEB (= DIP switch 5 to ON) in the following cases:
– Ethernet host connection
– RS-485 host connection, provided only one AMC2 is connected on the bus.
Set BPA (= DIP switch 5 to OFF) in the case of an:
4 RS-485 host connection with more than one and maximum eight AMC2s per bus.