DC09 acct1 length 0501 – 0502 06
DC09 acct1 0503 – 0518 000004
000000
0000
DC09 acct2 length 0519 – 0520 06
DC09 acct2 0521 – 0536 000004
000000
0000
DC09 Lpref 0544 – 0549 000000
DC09 Rrcvr enable 0537 0
DC09 Rrcvr 0538 – 0543 000001
Notice!
Enter a telephone number when the Contact ID or SIA is selected. Enter an IP address and
port number when the Conettix IP is selected. Anti-replay for receiver, acknowledge wait time
for receiver, and network polling time for receiver are valid only when Conettix IP is used.
How to program an IP address and port:
1. Program an IP address with 17 digits: digits 1 - 12 for the IP address and 13 - 17 for the
port.
2. Use no punctuation in the IP address.
3. If any unit of the IP address has less than 3 digits, use 0 to fulfill the data in the higher
bits.
4. The remaining 5 digits program the port. Port number ranges from 0-65535.
5. If a port number has less than 5 digits, use 0 to fulfill the data.
Example
4 To program the IP address “10.16.1.222:80”, enter the following sequence into the
correspondent address:
[0 1 0 0 1 6 0 0 1 2 2 2 0 0 0 8 0]
Reports Programming
System Reports
Option Address Default
Zone status restore report 0120 6
AWAY arming / disarming report 0121 6
EN=1/5/6/7
STAY arming / disarming report 0122 6
EN=1/5/6/7
System status report (zone fail, comm. fail, telephone line
fail, AC fail, low battery and so on.)
0123 6
EN=1/5/6/7
Keypad panic alarm report 0124 0
Keypad fire alarm report 0125 0
8.1.2
AMAX panel Address Programming | en 113
Bosch Sicherheitssysteme GmbH Installation Manual 2015.05 | 06 | F.01U.309.277