Zone
When the key-switch operates the arm/disarm, the keypad sounds two beeps and report sent
to the system by user code 254.
Notice!
When the key-switch operates the arm/disarm successfully, the siren sounds short to indicate
it.
16 – Key STAY Toggle
The key switch momentary STAY zone type performs as described below:
1. Disarm:
Zone normal - no action
Zone triggered - activate STAY arm / report
2. AWAY Arm:
Zone normal - no action
Zone triggered - activate disarm / report
3. STAY Arm: same as AWAY arm performance
This zone will ignore all other programming items, such as bypass, forcing arm.
When the system is armed in this mode, the keypad activates two beeps and report sent is by
user code 254.
17 – Key STAY on/off
The key switch on/off STAY zone type performs as described below:
1. Disarm:
Zone normal - no action
Zone triggered - activate STAY arm / report
2. AWAY Arm:
Zone normal - activate disarm / report
Zone triggered - no action
3. STAY Arm: same as AWAY arm performance
When the key-switch operates the arm / disarm, the keypad sounds two beeps and report sent
to the system by User Code 254.
Notice!
When the key-switch operates the arm/disarm successfully, the siren sounds short to indicate
it.
18 – 24-Hour Panic
The 24-hour panic zone type performs as described below:
1. Disarm:
Zone normal - no alarm / no report
Zone triggered – silent alarm / report
2. AWAY Arm: