26 – Instant Report
The instant report zone type performs as described below:
1. Disarm:
Zone normal – no action
Zone triggered – report
2. AWAY Arm: same as disarm performance
3. STAY Arm: same as disarm performance
Zone in Area
Each zone is assigned to an area. This assignment influences the way how zones are indicated
on keypads. For more information, please refer to Zone Indication Keypad and Event Log, page
68.
RF Zones
AMAX 3000 / 3000 BE / 4000 identifies RF zones by Zone RFID. AMAX Keypad programming
supports entering RFID automatically for Radion devices. When zone RFID is asked, press *
button for 3 second toggles between AUTO and MANUAL mode. When MANUAL is selected,
enter 9 – digit RFID using pin keys. When AUTO is selected, trigger RF device in order to enter
RFID automatically.
Hardwired Input Zones
On-board Inputs:
The AMAX panel provides onboard hard-wired inputs. An additional input is provided for the
enclosure tamper.
On-board Zone Response Time:
The AMAX panel supports different response times for the onboard zones. The response time
value range is 000.0-999.9 seconds.
On-board Zone EOL
Single EOL: If the zone tamper function is not selected, each zone uses a single 2.2 kilo ohm
EOL. The panel can detect the zone as short, normal or open.
Loop Resistance (ohm)
Zone Status
Min Type Max
0 1430 triggered
1650 2200 2750 normal
2970 triggered
The detectors (sensors) will be connected between zone and COM terminal through EOL
series (open triggered) or parallel connection (short triggered).
COM
Zone
62
en | Settings AMAX panel
2015.05 | 06 | F.01U.309.277 Installation Manual Bosch Sicherheitssysteme GmbH