If the zone is programmed to disable 24-hour zone tamper, the wiring method for single-
terminal resistor is required. If the zone detests alarm, the zone will process according to
specified zone type.
Zone Status Reporting
The AMAX panel reports the zone status according to the specified path, including alarm, zone
fault, zone bypass and zone tamper alarm.
Zone Chime Mode
The system will support the chime mode.
The process is as follows:
If the chime mode is used and a zone is triggered the keypad buzzer will sound for 1
second (only in disarmed status).
Zone Pulse Count
The system will support the pulse count mode.
The process is as follows:
Pulse count duration time must be configured (refer to Pulse Count Duration Programming,
page 131)
Pulse count for a zone can be set to a value between 1 and 9 (0 = disabled)
The process is as follows:
An alarm is created only if the zone is triggered as many times as the value “pulse count”
within the time “count duration”
Domestic no.
The system supports domestic call mode.
The process is as follows:
If the domestic call mode is configured for a zone and an alarm from this zone is created
the alarm will be reported via the onboard voice dialer to the destination(s) configured
and needs acknowledgement.
Cross Zone
The cross zone option works as follows:
Prerequisites:
At least two zones in the same area have option cross zone enabled
System option cross zone timer is set to a value higher than 0
When one of these zones is triggered for more than 20 seconds, an alarm is created.
When one of these zones (the first zone) is triggered for a shorter time than 20 seconds, the
cross zone timer starts, no alarm is created at this time
When no more zones (with cross zone option) are triggered within the cross zone time,
no alarm is created
When the first zone is triggered twice or more within the cross zone time, no alarm is
created
When a second zone or further zones (with cross zone option) is / are triggered within
the cross zone time, then an alarm is created for all triggered zones
When the first zone or one of the other zones (with cross zone option) is / are triggered
twice or more after cross zone time is expired, the timer restarts
AMAX panel
Settings | en 67
Bosch Sicherheitssysteme GmbH Installation Manual 2015.05 | 06 | F.01U.309.277