R5INIT
4--1
1070 072 196-101 (00.06) GB
4R5INIT
4.1 Characteristics
Characteristics R5INIT
Module name R5INIT
Number of parameters 6
Reserved markers M230 to M254
Communication Modules
The initialization R5INIT function module creates different tables in the ZS
Central Unit and on the COM-E module, and fills them out with information
which is accessed during communication between these modules.
Before communication via the computer interface is possible, this module
must and shall only be processed once after having switched on the control-
ler. In general, it is therefore called up in the OM5 or OM7 startup-organiza-
tion module.
. In case of usage as a server only, the R5INIT module is not required.
4.2 Parameters
The R5INIT has 5 input and one output parameter.