General Information Regarding BUEP-E and BUEP19E
7--12
1070 072 196-101 (00.06) GB
Read PLC Operating Mode 7A
H
Command Identification Command
Type of command E
Command code 7A
H
Command attribute 0
Address high part ZS/SK block address
Address low part 0
Type of operand 0
The command provides 1 word (= 2 bytes) status code.
. Only permitted as PST command!
Description of the status code:
High Byte Low Byte
0 7 6 5 4 3 2 1 0
Status code of SK500: (Block address = 0xff)
Bit 0 0
1
CLAB activ e
CLAB not active
Bit 1 to 3 x Reserved
Bit 4 0
1
System in RUN
System in STOP
Bit 5 to 7 x Reserved
Status code of ZS500/ZS400:
Bit 0 0
1
Module in RUN
Module in STOP
Bit 1 x Reserved
Bit 2 0
1
Outputs disabled
Outputs enabled
Bit 3 to 7 x Reserved