General Information Regarding BUEP-E and BUEP19E
7--16
1070 072 196-101 (00.06) GB
Error during command execution on the partner module PST
Error Information [hex] Explanation
Reaction Class Code PW
01 40 02 Memory access error
03 40 03 4 Wrong memory type, e.g. write access on EPROM
01 40 05 Internal error during processing of the command on the PST
03 40 10 10 No module exists for the specified PST block address
03 40 20 5 PST command code unknown
03 40 23 13 Invalid coordination marker on the PST
03 40 26 12 Block length error
03 40 3A 4, 11 Wrong address orientation, e.g. writing a word on odd addresses
03 40 3B 11 Invalid address range
03 40 3C 9 Invalid parameter
03 40 3D 4 Invalid type of operand
03 40 63 Buffer overflow; data length is greater than the available memory of 200
H
bytes.
03 40 D2 13 Coordination marker disabled.
01 40 xy Module-specific error.
01 41 20 STOP error; the module is in the STOP state. The specified command
cannot be executed.
01 41 21 RUN error; command cannot be executed in RUN.
03 41 23 4, 5 Field access not allowed; the desired access (read/write/bit) is not appli-
cable for this field.
01 41 24 Field protection active; at the moment, the desired field is reserved by
another position.
01 41 25 Timer disabled; actual time values can only be changed when time is
running.
03 41 26 9 Module number too high; higher than the allowed maximum value.
03 41 27 9 Data module not available, in the PST.
03 41 28 11 Data module too small, in the PST.
03 41 2B Data Error during writing on the system clock.
01 41 xy Module-specific error.