Service
47
Control 8313 – 6720859567 (2017/03)
Incorrect
FM-SI/EMS
module
Heat source does not start. Invalid combination of EMS heat source
with FM-SI
Incorrect boiler type selected.
The EMS boiler type does not support the
FM-SI module.
Check boiler type setting.
Remove FM-SI.
Open safety chain (SI 17,18)
at ZM5313.
Connect safety equipment to the
EMS heat source.
Open safety chain (SI 17,18)
at ZM5313.
Remove the function module.
Wrong conn.
pos. for EMS SI
chain
Heat source does not start. Incorrect connection of safety equipment.
Incorrect boiler type selected.
Connect safety equipment to the
EMS heat source.
Check boiler type setting.
With the EMS boiler type, open safety
chain (SI 17, 18) at the ZM5313
(remove jumper).
Wrong
connection for
flue gas shut-
off valve EMS
Heat source does not start. The flue gas damper is incorrectly
connected.
Connect the flue gas damper to the SAFe.
The flue gas
damper on the
central module
is not
supported for
the boiler type
EMS. Please
insert the
jumper.
Incorrect boiler selected.
Incorrect connection location of flue gas
damper.
Check boiler type setting.
Connect flue gas damper to the EMS heat
source.
Flue gas
temperature
sensor for heat
source is
defective
The flue gas temperature cannot be
measured.
The temperature sensor is incorrectly
connected or faulty.
The temperature sensor or the control unit
is defective.
Check sensor port.
Replace the temperature sensor or
module.
Flue gas
temperature
too high
No effects on control characteristics The heat source is soiled.
The flue gas temperature sensor is faulty.
Clean heat source.
Check sensor connection and function.
External fault
input on
heating circuit
pumpExternal
fault input on
heating circuit
pump
No effects on control characteristics The error input WF1/2 of the FM-MM
module has been opened.
The externally connected heating circuit
pump is faulty or malfunctioning.
Check the function of the externally
connected heating circuit pump.
Replace the module if necessary.
Use of control
unit
address 0 is bl
ocked
No effects on control characteristics The rotary encoder on the rear of the user
interface is addressed incorrectly.
Example: system with a control unit and
rotary encoder position > 0.
Check the position of the rotary encoder
( Chapter 8.2.1, page 16):
Position 0: master control unit
(only 1 CBC-BUS node exists)
Position > 0: additional CBC-BUS
node exists
No master
controller
connected
Boiler protection is not ensured.
DHW priority is no longer possible.
The control expects the minimum
outdoor temperature.
The master control unit (address 0)
is switched off.
No master (address 0) available
Check addresses of all CBC-BUS nodes.
The master control unit must have the
address 0 (rotary encoder behind the
user interface of the control unit
Chapter 8.2.1, page 16).
Check CBC-BUS connection to
address 1.
Connection to
sub station
disrupted
CBC-BUS communication no longer
possible.
Control functions requiring data
exchange via the CBC-BUS can no
longer be executed.
Several addresses are identical.
Each address must only be assigned once in
the CAN-BUS network.
Check addresses of all CBC-BUS nodes.
Each address must only be assigned once
in the CBC-BUS network.
Fault,
observation
Effect on control characteristics Reason Remedy

Table of Contents

Other manuals for Bosch Control 8313

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch Control 8313 and is the answer not in the manual?

Bosch Control 8313 Specifications

General IconGeneral
BrandBosch
ModelControl 8313
CategoryControl Unit
LanguageEnglish

Related product manuals