System settings (Service menu – Settings)
6
Circulation
2)3)
Is a circulation pump
installed?
Yes, No no
How frequently should the
circul. pump be switched on
per hour?
once for 3
minutes, twice for
3 minutes, 3 times
for 3 minutes, 4
times for 3
minutes, 5 times
for 3 minutes, 6
times for 3
minutes,
permanent
operation
twice for 3
minutes
Switch on circ. pump Graphical display of number of
times the pump is switched on
per hour.
Do you wish to change the
circulation switching
programme?
Yes, No no When selecting “yes” the
system jumps to the DHW
circulation switching program.
Thermal disinfection
2)
Should a thermal
disinfection be carried out?
Yes, No no
At which temperature
should the thermal
disinfection take place?
60 °C to 80 °C
4)
70 °C At temperatures above 60 °C
there is a risk of scalding at the
draw-off points during and after
thermal disinfection!
On which day of the week
should the thermal
disinfection take place?
Monday, Tuesday,
Wednesday,
Thursday, Friday,
Saturday, Sunday,
daily
Tuesday
At which time should the
thermal disinfection take
place?
00:00h to 23:00h 1:00h Times entered must be whole
hours only (no minutes).
Menu item Input range
Standard
setting Other information
Table 16 Navigator for service menu SETTINGS\DHW