17.2.10 Group E3: PID Function
PID basic configuration
Function
code
Name Setting range
Min.
unit
Factory
default
Attribute
E3.00
PID reference
channel
0: No PID control
1: Panel potentiometer
2: Panel digital setting
3: Analog input AIV
4: Analog input AIC
5: Analog digital
setting [E3.03]
6: Rotation speed
digital setting [E3.04]
7: Communication
1 0 STOP
E3.01
PID feedback
channel
0: AIC
1: AIV
1 0 STOP
E3.02 Reserved
E3.03
Analog
digital setting
0.00 ~ 10.00 V 0.01 0.00
RUN/
STOP
E3.04
Rotation speed
digital setting
0 ~ 30000 rpm 1 rpm 0 rpm
RUN/
STOP
E3.05
~
E3.09
Reserved
PID control
Function
code
Name Setting range
Min.
unit
Factory
default
Attribute
E3.10
P: Proportional
gain
0.0 ~ 10.000 0.001 1.500
RUN/
STOP
E3.11 Ti: Integral time
0.00 ~ 100.00s
(0.00 represents no integral)
0.01s 0.00s
RUN/
STOP