Function
code
Name Setting range
Min.
unit
Factory
default
Attribute
E3.12
Td: Derivative
time
0.00 ~ 100.00s
(0.00 represents no deriva‐
tive)
0.01s 0.00s
RUN/
STOP
E3.13
T: Sampling
period
0.01 ~ 100.00s 0.01s 0.50s
RUN/
STOP
E3.14
Deviation
limit
0.0 % ~ 20.0 % (closed loop
reference value)
0.1 % 2.0 %
RUN/
STOP
E3.15
PID
regulation
mode
0: Stop integral adjustment,
when frequency arriving at
upper/lower limit
1: Continue integral adjust‐
ment, when frequency arriv‐
ing at upper/lower limit
1 0
RUN/
STOP
17.2.11 Group E4: Protection and Fault
Protection configuration
Function
code
Name Setting range
Min.
unit
Factory
default
Attribute
E4.00 Reserved
E4.01
Overvoltage
prevention
setting
0: both disabled
1: Stall protection enabled,
braking disabled
2: Stall protection disabled,
braking enabled
1 0 STOP
E4.02
Stall overvolt‐
age preven‐
tion level
200V class: 300 ~ 390 V
400V class: 600 ~ 885 V
1 V
390 V
885 V
STOP
E4.03
Stall overcur‐
rent preven‐
tion level
20.0 % ~ 200.0 %
(Rated frequency converter
output current)
0.1 % 200.0 % STOP
E4.04
Low speed de‐
rating frequen‐
cy
0.10 ~ 300.00 Hz 0.01 Hz 25.00 Hz
RUN/
STOP
E4.05
Zero speed
load
25.0 % ~ 100.0 % 0.1% 25.0 %
RUN/
STOP