Function
code
Name Setting range
Min.
unit
Factory
default
Attribute
E4.06
Phase loss
protection
0: Both input and output
phase loss protection active
1: Only input phase loss pro‐
tection active
2: Only output phase loss
protection active
3: Both input and output
phase loss protection inactive
1 3
RUN/
STOP
E4.07
~
E4.14
Reserved – – – –
Fault reset
Function code
Name Setting range
Min.
unit
Factory
default
Attribute
E4.15
Number of fault
reset attempts
0 ~ 3
(0: No auto reset)
1 0 STOP
E4.16
Interval between
reset attempts
2 ~ 60s 1s 10s STOP
E4.17 ~ E4.19 Reserved – – – –
Error code memory
Function code
Name
Setting
range
Min.
unit
Factory
default
Attribute
E4.20 Last fault type
0 ~ 51
1 0 read only
E4.21 Second last fault type 1 0 read only
E4.22 Third last fault type 1 0 read only
E4.23 ~ E4.29 Reserved – – – –
● 0: No error
● 1: OC-1, means overcurrent happens when constant speed running
● 2: OC-2, means overcurrent happens when acceleration
● 3: OC-3, means overcurrent happens when deceleration
● 4: OE-1, means overvoltage happens when constant speed running
● 5: OE-2, means overvoltage happens when acceleration
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Bosch Rexroth AG
Appendix