EasyManua.ls Logo

Bosch Rexroth EFC 3600 - Page 223

Bosch Rexroth EFC 3600
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function
code
Name Setting range
Min.
unit
Factory
default
Attribute
E4.06
Phase loss
protection
0: Both input and output
phase loss protection active
1: Only input phase loss pro‐
tection active
2: Only output phase loss
protection active
3: Both input and output
phase loss protection inactive
1 3
RUN/
STOP
E4.07
~
E4.14
Reserved
Fault reset
Function code
Name Setting range
Min.
unit
Factory
default
Attribute
E4.15
Number of fault
reset attempts
0 ~ 3
(0: No auto reset)
1 0 STOP
E4.16
Interval between
reset attempts
2 ~ 60s 1s 10s STOP
E4.17 ~ E4.19 Reserved
Error code memory
Function code
Name
Setting
range
Min.
unit
Factory
default
Attribute
E4.20 Last fault type
0 ~ 51
1 0 read only
E4.21 Second last fault type 1 0 read only
E4.22 Third last fault type 1 0 read only
E4.23 ~ E4.29 Reserved
0: No error
1: OC-1, means overcurrent happens when constant speed running
2: OC-2, means overcurrent happens when acceleration
3: OC-3, means overcurrent happens when deceleration
4: OE-1, means overvoltage happens when constant speed running
5: OE-2, means overvoltage happens when acceleration
DOK-RCON03-EFC-3600***-IT01-EN-P