6: OE-3, means overvoltage happens when deceleration
7: OL-1, means frequency converter overload
8: OL-2, means motor overload
9: EEP-, read/write EEP error, when read and write EEP/flash, error happens
10: SPI-, internal communication error
11: E-St, external fault
12: RS-, external communication error
13: CF, circuit fault, when there is something wrong with current detection
14: Reserved
15: OT, motor over temperature
16: CPU-, CPU is disturbed by external signal and program run to illegal address
17: SC, short circuit of IGBT happens
18: IPHL, input phase loss
19: OPHL, output phase loss
20: OH, frequency converter over temperature
21: PRSE, parameter set error
System status at the latest fault
Function
code
Name Setting range
Min.
unit
Factory
default
Attribute
E4.30 Output frequency at latest fault 0.00 ~ [b1.05] 0.01 0.00 read only
E4.31 Setting frequency at latest fault 0.00 ~ [b1.05] 0.01 0.00 read only
E4.32 Output current at latest fault 0.0 ~ 1000.0 0.1 0.0 read only
E4.33 Output voltage at latest fault 0 ~ 1000 V 1 0 read only
E4.34 DC bus voltage at latest fault 0 ~ 1000 V 1 0 read only
E4.35
Module temperature at latest
fault
1 0 read only