17.2.12 Group H0: Communication
General communication configuration
Function
code
Name Setting range
Min.
unit
Factory
default
Attribute
H0.00
Communication
protocol
0: ModBus 1 0 STOP
H0.01 Baud rate
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
1 3 STOP
H0.02 Data format
0: N, 8, 1 (1 start bit, 8 data
bits, 1 stop bit, no check)
1: E, 8, 1 (1 start bit, 8 data
bits, 1 stop bit, even parity)
2: O, 8, 1 (1 start bit, 8 data
bits, 1 stop bit, odd parity)
2: N, 8, 2 (1 start bit, 8 data
bits, 1 stop bit, no parity)
1 0 STOP
H0.03 Local address 1 ~ 247 1 1 STOP
H0.04
~
H0.07
Reserved – – – –
H0.08
Communication
disruption de‐
tection time
0.0 (invalid),
0.1 ~ 60.0s
0.1s 0.0s STOP
H0.09
Communication
disruption action
0: Freewheeling stop
1: Keep running
1 1 STOP