17.2.13 Group D: Monitoring Parameters
Monitoring parameters
Function
code
Name Setting range
Min.
unit
Factory
default
Attribute
d0.00 Output frequency 0.00 ~ 400.0 0.01 Hz 0 read only
d0.01 Output velocity 0 ~ 65535 rps 0 read only
d0.02 Setting frequency 0.00 ~ 400.0 0.01 Hz 0 read only
d0.03 Setting velocity 0 ~ 65535 1 0 read only
d0.04 Output voltage 0 ~ 480 1 V 0 read only
d0.05 Output current 0.0 ~ 1000.0 0.1 A 0 read only
d0.06 Output power 0.0 ~ 1000.0 0.1 kW 0 read only
d0.07 DC bus voltage 0 ~ 800 1 V 0 read only
d0.08 Analog input AIV 0.0 ~ 10.0 0.1 V 0 read only
d0.09 Analog input AIC 0.0 ~ 20.0 0.1 mA 0 read only
d0.10 Self-defined setting velocity 0.0 ~ 6000.0 0.1 0 read only
d0.11 Self-defined output velocity 0.0 ~ 6000.0 0.1 0 read only
d0.12 Digital input status 0 ~ 31 1 0 read only
d0.13 Digital output status 0 ~ 3 1 0 read only
d0.14 PID reference engineer value 0.0 ~ 6000.0 0.1 0 read only
d0.15 PID feedback engineer value 0.0 ~ 6000.0 0.1 0 read only
d0.16 Module temperature 1 0 read only
d0.17 Software version 1 0.00 ~ 99.99 0.01 * read only
d0.18 Software version 2 0.00 ~ 99.99 0.01 * read only
d0.19 Software version 3 0.00 ~ 99.99 0.01 * read only
d0.20 Actual carrier frequency 1 ~ 15 1 kHz * read only