[d0.10]=[d0.02] x [b0.32]
With:
[d0.10]: User-defined set velocity
[d0.02]: Set frequency
[b0.32]: User-defined proportion factor for velocity
User-defined output velocity
[d0.11]=[d0.00] x [b0.32]
With:
[d0.11]: User-defined output velocity
[d0.00]: Output frequency
[b0.32]: User-defined proportion factor for velocity
Users may convert the frequency to any other form they feel easy to understand via pa‐
rameter [b0.32].
PID reference engineering value
[d0.14]=PID reference x [b0.33]
With:
[d0.14]: PID reference engineering value
[b0.33]: PID reference / feedback coefficient
PID feedback engineering value
[d0.15]=PID feedback x [b0.33]
With:
[d0.15]: PID feedback engineering value
[b0.33]: PID reference / feedback coefficient
Users may convert the PID engineering value to any other form they feel easy to under‐
stand via parameter [b0.33].
In case the value of a monitoring parameter is too big to fit into the 4-digit
display:
If the display value is between 1000.0 and 9999.9, 1000 ~ 9999 is dis‐
played without the display of the decimal point.
If the display value is not less than 10000, the higher 4 digits are dis‐
played and the rightmost decimal point is lit to indicate that one more
digit is hidden to the right, for example: "12340" is displayed as "1234.".
Bosch Rexroth AG
Parameter Settings
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
58/235