Setting Exercise Timer
The generator is equipped with an exercise timer.
During the exercise period, the unit runs for
approximately 20 minutes and then shuts down.
Electrical load transfer DOES NOT occur during the
exercise cycle (unless an utility power outage occurs).
The generator will only enter the exercise cycle if the
unit is in the AUTO mode and this exact procedure is
followed.
To set the exercise timer:
NOTICE The generator is set with a service code
exercise cycle setting of Tuesday at 2:00 P.M, Central
Time. To change the cycle setting, proceed to the
following steps:
1. Choose the day and time you want your generator
to exercise.
2. Press and hold the left arrow and right arrow
simultaneously for 3 seconds to enter the General
Set-Up program mode. See General Set-Up flow
chart in Menu Section.
3. Verify and/or set the time and date on the unit.
4. Go to the SET EXERCISE prompt and hit the “OK”
button.
NOTICE Items will flash until they are selected.
SELECT DAY: Use the left or right arrow to toggle
through the days of the week, Once the day is
selected, hit the “OK” button.
SELECT HOUR: Use the left or right arrow to
toggle through between 1 and 12. Choose the
hour of day you want the generator to exercise
then hit the “OK” button.
SELECT MINUTE: Use the left of right arrow to
toggle between :00 and :59. Choose the minute of
the day you want the generator to exercise then
hit the “OK” button.
SELECT AM/PM: Use the left of right arrow to
toggle between AM and PM. Once chosen, hit the
“OK” button.
NOTICE During the weekly exercise cycle, the
generator will run for 20 minutes, but it will not supply
power to the home. During the exercise cycle, the in-
home monitor will continue blinking the GENERATOR
READY green LED.
If you want to change the day and time the unit
exercises, simply perform the procedure again.
To turn off the generator exercise cycle, go to the OFF
selection within the day of the week menu and press
OK. The display will then scroll: EXERCISE CYCLE
OFF.
Maintenance
Servicing the System
Before performing any generator maintenance, always
perform the following steps:
1. Set generator’s circuit breaker to its OFF position.
2. Press and hold the control board OFF button.
3. Remove 15 Amp fuse from control board.
4. Utility voltage is present at generator control
board. Disconnect power before servicing control
board by removing the fuses from the transfer
switch.
5. After all servicing has been completed, replace
fuses in transfer switch, replace 15 Amp fuse in
control board, set circuit breaker ON and press
and hold control board AUTO button.
Service Code Detection System
The generator may have to run for long periods of time
with no operator present. For that reason, the system
is equipped with sensors that automatically shut down
the generator in the event of potentially damaging
conditions, such as low oil pressure, high temperature,
over speed, and other conditions.
The generator’s control board shows service code
descriptions scrolling across the digital display. The
service code descriptions are listed below:
Low Battery Voltage
Low Oil Pressure
Under Voltage
Over Voltage
Engine Does Not Start
Low Frequency
Engine Overspeed
High Oil Temperature
Transfer Switch Service code
Battery Charge Circuit

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Briggs & Stratton Fortress and is the answer not in the manual?

Briggs & Stratton Fortress Specifications

General IconGeneral
Voltage120/240V
Frequency60 Hz
Fuel TypeGasoline
Wheel KitIncluded
Outlets(2) 120V 20A Outlets, (1) 120/240V 30A Locking Outlet