EasyManua.ls Logo

BT SWE120L - 4.4.3 Parameter 107 - battery size

BT SWE120L
230 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
Setting the parameters
© BT Repair manual SWE100, 120, 120L, 120S, 140, 140L, 200D 4 – 9
Order no.. Date Valid from serial no. T code
258946-120 2012-08-30 6061850- 841×842×843
4.4.3 Parameter 107 - battery size
You must state which type of battery the truck is equipped with. To
adjust the meter for battery charge level, consideration must be given
to the following:
Acid concentration when the battery is fully charged, in order to
check the battery's quality. The value should lie between 1.27-1.29.
Note that the acid concentration can vary depending on the make of
battery.
When the lifting capability is disconnected (the battery is discharged
to 80 %) the value should be close to 1.14 but no lower.
Free ventilated batteries
See the table below for the recommended parameter settings.
DANGER!
The battery's service life will be reduced if the value of parameter 107
is set to a value that is too high. The standard adjustment of
parameter 107 is set for normal handling of the truck. Other
applications may require a different adjustment of parameter 107.
Check that the parameter adjustment is right using the instructions
below.
Parameter 107 Battery size
Lead/acid battery
Battery size
Hawker Evolution
Battery size
Exide
Lower
discharge
Deeper dis-
charge
1
2
3
4
5
6 271-280 Ah 271-290 Ah
7 251-270 Ah 251-270 Ah
8 231-250 Ah 231-250 Ah
9 286-320 Ah 211-230 Ah 211-230 Ah
10 251-285 Ah 191-210 Ah 191-210 Ah
11 221-250 Ah 171-190 Ah 171-190 Ah
12 206-220 Ah 151-170 Ah 151-170 Ah
13 191-205 Ah 131-150 Ah 131-150 Ah
14 176-190 Ah 120-130 Ah 110-130 Ah
15 161-175 Ah
16 146-160 Ah
17 131-145 Ah
18 115-130 Ah
19
20
https://www.besttruckmanuals.com/

Table of Contents

Related product manuals