Operation 8
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements! 39
8 Operation
8.1 BC10 basic controller
The boiler is fitted with a control unit, the BC10 basic
controller. This controller can be used to control the heating
system.
z Push on the control panel (fig. 43) to get access to the
BC10 basic controller (fig. 44).
The BC10 basic controller has the following components:
Main power switch (pos. 1)
The main power switch is used to switch the boiler ON and
OFF.
"Reset" button (pos. 2)
If a fault has occurred you may have to restart the boiler by
pressing the "Reset" button.
This is only required in the event of a "locking" fault.
"Blocking" faults are reset automatically as soon as their
cause has been corrected. The display shows
[\/r/e| during
the reset operation.
“Chimney sweep" button (pos. 3)
The "Chimney sweep" button is used to put the boiler into
flue gas test, service or manual operation mode. The BC10
maximum heating water temperature setting applies.
–The flue gas test enables the boiler to be run in full-load
operation manually for a short period. See table 8, "Flue
gas test", page 41.
–The service mode enables the boiler to be run in part-
load operation manually for a short period.
Measurements and settings can be carried out on the
boiler. See table 9, "Service mode", page 42.
Fig. 43 Opening the control panel
Fig. 44 BC10 basic controller
pos. 1: Main power switch
pos. 2: "Reset" button
pos. 3: "Chimney sweep" button
pos. 4: "Service" button
pos. 5: Service Tool Connector
pos. 6: LED "Burner operation"
pos. 7: LED "Central heat demand"
pos. 8: Space heating water temperature knob
pos. 9: Display
pos. 10: DHW temperature knob
pos. 11: LED "DHW demand"
888
1
123 456
11
10 98
7
110
140
130
120
90
100
130
170
150
90
110
190
CAUTION
Limit the space heating water temperature to the
maximum flow temperature of the floor heating
circuit.
CAUTION
A power interruption discontinues manual
operation. Frost damage may occur.