Display information 13
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements! 73
13.2 Replacing the control panel
z Take the control panel from the boiler frame.
z Install the control panel in the boiler door by following the
above procedure in reverse order.
13.3 BC10 Display readings
13.4 BC10 Display settings
Display readings
Display
reading
Key to display reading Unit Range
Remarks
[\7\5|
Current space heating water temperature °F
[\/\/0|
–
[1/9/0|
[p/2\2|
Current system pressure psi
[p/0.0|
–
[p/5/8|
Table 17 BC10 Display readings
Display settings
Display
setting
Meaning of display setting Unit Range
Factory-
adjusted
setting
[l/9/9|
Sea level (0-4,000 ft):
configured target load (GB162-80 kW)
%
[l/2/5|
–
[l/9/9|
/
[l/??/|
100 %
[l/??/|
High altitude (4,000-10,000 ft) :
configured target load (GB162-80 kW)
%
[l/3/6|
–
[l/9/9|
/
[l/??/|
100 %
[l/??/|
Sea level (0-4,000 ft):
configured target load (GB162-100 kW)
%
[l/2/0|
–
[l/9/9|
/
[l/??/|
100 %
[l/??/|
High altitude (4,000-10,000 ft):
configured target load (GB162-100 kW)
%
[l/3/0|
–
[l/9/9|
/
[l/??/|
100 %
[l/??/|
[f/\/5|
Configured target value of the pump
run-over time.
NOTE: Do not set the pump run-over
time to less than [f/\/5| (= 5 minutes).
min.
[f/0/0|
–
[f/6/0|
/
[f/1/d|
24 h
[f/\/5|
[c/\/1|
DHW flow operating condition setting.
NOTE: If the setting [c/\/0| is displayed,
the frost protection of the DHW flow has
also been switched off.
–
[c/\/0|
"Off" /
[c/\/1|
"On"
[c/\/1|
Table 18 BC10 Display settings