EasyManua.ls Logo

Buderus Logamax plus - Test the Ignition Safety Shut off Device

Buderus Logamax plus
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Start-up procedure 9
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements! 57
z Connect the multimeter in series (fig. 68).
Select the µA DC range on the multimeter. The multim-
eter must have a resolution of at least 1 µA.
z Switch ON the heating system by pressing the main
switch of the BC10 basic controller (fig. 66, pos. 1).
z Activate the Service mode in accordance with the
"Service mode" menu (table 9, page 42).
z Set the capacity to minimum (part load) according to the
"Service mode" menu (table 9, page 42).
z After the LED "Burner operation" (fig. 66, pos. 6) has lit
wait for one minute until the boiler is burning at part load.
z Measure the ionization current. The ionization current
must be > 5 µA DC at part load operation.
z Enter the result in the start-up report (see paragraph 15.1
"Start-up report", page 85).
z If the result is not as it should be, check the gas/air ratio
(paragraph 9.8, page 52) or check the ionization elec-
trode (paragraph 12.3.4, page 68).
z Press and hold the "Chimney sweep" button (fig. 66,
pos. 3) (approx. two seconds), until the dot in the right-
hand bottom corner of the display (fig. 66, pos. 9)
appears. See also table 8, "Flue gas test", page 41.
z Switch OFF the heating system by pressing the main
switch of the BC10 basic controller (fig. 66, pos. 1).
z Remove the multimeter and reconnect the monitoring
cable.
z Switch ON the heating system by pressing the main
switch of the BC10 basic controller (fig. 66, pos. 1).
z Check that the boiler performance is still at the required
value. See the "Service mode" menu (table 9, page 42).
9.13 Test the Ignition Safety shut off device
z Switch OFF the heating system by pressing the main
switch of the BC10 basic controller (fig. 66, pos. 1).
z Disconnect the plug and socket connection of the moni-
toring cable.
z Switch ON the heating system by pressing the main
switch of the BC10 basic controller (fig. 66, pos. 1).
z Press the "Chimney Sweep"
d button and hold it (for
approx. two seconds), until the display shows the
decimal point.
z Check if the boiler does one start-up attempt and three
restart attampts.
After each start-up attempt the boiler will signal a start-up
failure. A "6A" code can be seen in the display.
After the last start-up attempt, the boiler will lock out.
The "6A" code is blinking in the display.
z Connect the plug and socket connection of the moni-
toring cable.
Fig. 68 Measuring the ionization current

Table of Contents

Other manuals for Buderus Logamax plus

Related product manuals