EasyManua.ls Logo

Buderus Logamax plus - Performance Testing and Adjustments

Buderus Logamax plus
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Start-up procedure9
Logamax plus GB162-80 kW/100 kW - Subject to modifications resulting from technical improvements!52
z Close the gas valve.
z Remove the gauge-connection tube and tighten the
screw plug on the testing nipple again.
z Open the gas valve again by pushing on the gas valve
and turning it ¼ rotation in a counterclockwise direction.
9.8 Check and adjust the gas/air ratio
z Open at least two thermostatic radiator valves, if present.
Do not switch ON the boiler.
z Push on the control panel to open it.
z Switch OFF the heating system by pressing the main
switch of the BC10 basic controller (fig. 59, pos. 1).
z Close the gas valve (fig. 56).
z Turn the vent key through a quarter rotation to undo the
boiler door lock (fig. 47, see detailed picture).
z Push the fastener down (fig. 47) and open the boiler
door.
z Open the screw plug on the testing nipple for the burner
pressure by 2 turns (fig. 60, pos. 1).
z Set the pressure gauge to "0".
z Use a connection tube to connect the positive port of the
pressure gauge to the testing nipple for burner pressure
(fig. 60, pos. 2).
NOTICE
z Check the gas supply pipe or contact the rele-
vant gas utility company if the required supply
pressure is not available.
z If the supply pressure is too high, a gas pres-
sure regulator must be integrated upstream of
the gas fitting. Contact the gas utility
company.
Fig. 59 BC10 basic controller
888
1
123 456
11
10 98
7
110
140
130
120
90
100
130
170
150
90
110
190
WARNING
Damage to the boiler by incorrect adjustment of
the gas/air ratio.
z Adjust gas/air ratio ONLY with part load!
z Adjust gas/air ratio ONLY based on the gas/
air pressure differential and never based on
measured flue gas values such as CO/CO
2
/
NO
X
!
Fig. 60 Checking the gas/air ratio
2
1
NOTICE
Throughout the measuring operation, keep the
digital pressure gauge in the same position
(horizontal or vertical) in which it was reset
to "0".

Table of Contents

Other manuals for Buderus Logamax plus

Related product manuals