47
Adjustment and commissioning
→ Release the push button when desired
number of LEDs is on.
To set the units for the low switching threshold.
→ Briey press push button
After 2s, next LED ashes;
1ash=1% of the FS
If low switching threshold set to 24%, LED no. 3
ashes 9 times then stays on;
1ash=1% of the FS
Next LEDS come on one after the other until
they show the factor of ten for the current high
switching threshold;
1LED ON=10% of the FS
A
If high switching threshold set to 82%, LED no.9
ashes 9times then stays on;
1ash=1% of the FS
Next LEDS come on one after the other until
they show the factor of ten for the current low
switching threshold;
1LED ON=10% of the FS
→ Release the push button when desired number
of LEDs is on.
To set the units for the high switching threshold.
→ Briey press push button
After 2s, next LED ashes;
1 ash=1% of the FS
→ Release push button when LED has ashed the desired
number of times
B
C
Fig.41: Settingtherelayswitchingthresholds,part2
english
Type 8041