Technical data
6 TECHNICAL DATA
6.1 Conditions of use
Ambient temperature
–10...+60 °C
Air humidity
< 85%, without condensation
Use
Indoor and outdoor
Protect the device against electromagnetic interference, ultravio-
let rays and, when installed outdoors, the effects of the climatic
conditions.
IP-Code
1) not evaluated by UL
IP67
1)
and IP65
1)
according to IEC / EN 60529
Mating connectors must be wired, plugged, and tightened.
Housing lid must be fully tightened and locked
Operating condition
Continuous operation
Equipment mobility
Fixed device
Degree of pollution
Degree 2 according to UL/EN 61010 -1
Installation category
Category I according to UL/EN 61010-1
Maximum height above sea level
2000 m
6.2 Conformity to standards and directives
The applied standards, which verify conformity with the EU directives, can be found on the EU-type examination
certificate and/or the EU declaration of conformity (if applicable).
6.2.1 Conformity to the Pressure Equipment Directive
Make sure that the device materials are compatible with the fluid.
Make sure that the pipe DN is adapted for the device.
Observe the fluid nominal pressure (PN) for the device. The nominal pressure (PN) is given by the device
manufacturer.
The device conforms to Article 4, Paragraph 1 of the Pressure Equipment Directive 2014/68/EU under the fol-
lowing conditions:
Device used on a piping (PS = maximum admissible pressure; DN = nominal diameter of the pipe)
Type of fluid Conditions
Fluid group 1, Article 4, Paragraph 1.c.i DN≤25
Fluid group 2, Article 4, Paragraph 1.c.i
DN≤32
or PSxDN≤1000 bar
Fluid group 1, Article 4, Paragraph 1.c.ii
DN≤25
or PSxDN≤2000 bar
Fluid group 2, Article 4, Paragraph 1.c.ii
DN≤200
or PS≤10 bar
or PSxDN≤5000 bar