The following table lists the electrical data relating to the power supply
of the various models and the specifi cations of each. Note that some
models may be powered at diff erent voltages, obviously with diff erent
power input and steam production.
power supply nominal specifi cations
model steam
production
(2; 4)
(kg/h)
(lbs/hr)
power
(2)
(kW) code voltages
(1)
(V - type)
current
(2)
(A)
TAM confi guration
(5)
cable
(3)
(mm
2
) /
(AWG)
recommended
External fuses
sizes
(3)
(A / type)
wiring
diagram
(Fig.)
UE001 1,5 / 3.3 1,1 U 208 - 1~ 5,4 13.a 100 1,5 / 16 10 A /fast blow 10.a
D 230 - 1~ 4,9 13.a 100 1,5 / 16 10 A / fast blow 10.a
UE003 3,0 / 6.6 2,2 U 208 - 1~ 10,8 13.d 300 2,5/14 16 A / fast blow 10.a
D 230 - 1~ 9,8 13.d 300 2,5/14 16 A / fast blow 10.a
W 208 - 3~ 6,2 13.a 100 1,5 / 16 10 A / fast blow 10.b
K 230 - 3~ 5,6 13.a 100 2,5/14 16 A / fast blow 10.b
M 460 - 3~ 2,8 13.d 100 1,5 / 16 10 A / fast blow 10.b
UE005 5,0 / 11.0 3,7 U 208 - 1~ 18,0 13.e 300 6/10 32 A / fast blow 10.a
D 230 – 1~ 16,3 13.e 300 6/10 32 A / fast blow 10.a
W 208 - 3~ 10,4 13.c 300 2,5/14 16 A / fast blow 10.b
K 230 - 3~ 9,4 13.c 300 2,5/14 16 A / fast blow 10.b
M 460 - 3~ 4,7 13.a 100 1,5 / 16 10 A / fast blow 10.b
N 575 - 3~ 3,8 13.a 100 1,5 / 16 10 A / fast blow 10.b
UE008 8,0 / 17.6 6,0 W 208 - 3~ 16,7 13.c 300 6/10 32 A / fast blow 10.b
K 230 – 3~ 15,1 13.c 300 6/10 32 A / fast blow 10.b
M 460 - 3~ 7,5 13.a 100 2,5/14 16 A / fast blow 10.b
N 575 – 3~ 6,0 13.a 100 2,5/14 16 A / fast blow 10.b
UE009 9,0 / 19.8 6,7 U 208 - 1~ 31,37 13.a 500 16/6 50A / fast blow 10.a
D 230 - 1~ 29,3 13.a 500 10/8 40 A / fast blow 10.a
UE010 10,0 / 22.0 7,5 W 208 - 3~ 18,8 13.c 300 6/10 32 A / fast blow 10.a
K 230 – 3~ 10,8 13.c 300 2,5/14 16 A / fast blow 10.b
M 460 - 3~ 9,4 13.a 100 2,5/14 16 A / fast blow 10.b
N 575 – 3~ 7,5 13.d 300 2,5/14 16 A / fast blow 10.b
UE015 15,0 / 33.0 11,2 W 208 - 3~ 31,2 13.c 500 10/8 40 A / fast blow 10.b
K 230 – 3~ 28,2 13.c 500 16 / 0 32 A / fast blow 10.b
M 460 - 3~ 14,1 13.a 300 10/8 20 A / fast blow 10.b
N 575 – 3~ 11,3 13.a 300 4 / 10 16 A / fast blow 10.b
UE018 18 / 39.7 13,5 M 460 - 3~ 16,9 13.a 500 6 / 10 32 A / fast blow 10.b
N 575 – 3~ 13,57 13.a 500 6 / 10 32 A / fast blow 10.b
UE025 25 / 55.1 18,7 W 208 - 3~ 52,0 13.b 500 25 / 3 80 A / fast blow 10.c
K 230 – 3~ 47,1 13.b 500 25 / 3 63 A / fast blow 10.c
M 460 - 3~ 23,5 13.c 500 10/8 32A / fast blow 10.c
N 575 – 3~ 18,8 13.c 500 6/10 25A / fast blow 10.c
UE035 35 / 77.2 26,2 W 208 - 3~ 72,9 13.c 700 35 / 4 100 A / fast blow 10.c
K 230 – 3~ 65,9 13.c 700 35 / 4 100 A / fast blow 10.c
M 460 - 3~ 32,9 13.c 500 16 / 6 50 A / fast blow 10.c
N 575 – 3~ 26,4 13.c 500 10/8 40 A / fast blow 10.c
UE045 45 / 99.2 33,7 W 208 - 3~ 93,68 13.b 700 70 / 2 125 A / fast blow 10.d
K 230 – 3~ 84,72 13.b 700 70 / 2 125 A / fast blow 10.d
M 460 - 3~ 42,4 13.c 700 16 / 6 60 A / fast blow 10.c
N 575 – 3~ 33,9 13.c 700 16 / 6 50 A / fast blow 10.c
UE065 65 / 143.3 48,7 M 460 - 3~ 61,19 13.b 700 35 / 4 100 A / fast blow 10.d
N 575 – 3~ 48,95 13.b 700 35 / 4 80 A / fast blow 10.d
Tab. 11.a
(1)
tolerance allowed on the rated mains voltage: -15%, +10%;
(2)
tolerance on the rated values: +5%, -10% (EN 60335-1);
(3)
recommended values refer to laying PVC or rubber cables in closed
conduits, 20 m (65.6 feet) long; use the local standards, or whichever is more restrictive,
(4)
rated max instant steam production: the average steam production
may be aff ected by external factors, such as: ambient temperature,
water quality, steam distribution system;
(5)
refer to the wiring diagrams to verify
the data are not absolute and if these diff er from local standards,
the latter must prevail.