37
ENG
“UE BASIC” +03U0042EN - rel. 1.3 - 10 May 2013
11.5 Models of linear distributors and typical installations
UEY models
code
UE001Y
UE003Y
UE005Y
UE008Y
UE009Y
UE010Y
UE015Y
UE018Y
UE025Y
UE035Y
UE045Y
UE045Y
( 230V )
UE065Y
Ø steam outlet mm (in) 22
(0.9”)
22
(0.9”)
30
(1.2”)
30
(1.2”)
30
(1.2”)
30
(1.2”)
30
(1.2”)
30
(1.2”)
40
(1.6”)
40
(1.6”)
40
(1.6”)
2x40
(2x1.6”)
2x40
(2x1.6”)
max. capacity
kg/h (lb/h)
1/1.5
(2.2/3.3)
3
(6.6)
5
(11)
8
(17.6)
9
(19.8)
10
(22)
15
(33)
18
(39.7)
25
(55.1)
35
(77.2)
45
(99.2)
45
(99.2)
65
(143.3)
CAREL DP linear distributors
cod. Ø isteam
inlet
mm (in)
max.
capacity
Kg/h (lb/h)
length
mm (in)
DP035D22R0 22 (0.9”) 4 (8.8) 332 (13.1) 1 1 --------- - -
DP045D22R0 22 (0.9”) 6 (13.2) 438 (17.2) 1 1 --------- - -
DP060D22R0 22 (0.9”) 9 (19.8) 597 (23.5) 1 1 --------- - -
DP085D22R0 22 (0.9”) 9 (19.8) 835 (32.9) 1 1 --------- - -
DP035D30R0 30 (1.2”) 5 (11) 343 (13.5) - - 1 -------- - -
DP045D30R0 30 (1.2”) 8 (17.6) 427 (16.8) - - 1 1 ------- - -
DP060D30R0 30 (1.2”) 12 (26.5) 596 (23.5) - - 1111- - - - - - -
DP085D30R0 30 (1.2”) 18 (39.7) 850 (33.5) - - 111111(2)* - - - -
DP105D30R0 30 (1.2”) 18 (39.7) 1048 (41.3) - - 111111(2)* - - - -
DP125D30R0 30 (1.2”) 18 (39.7) 1245 (49) - - 111111(2)* - - - -
DP085D40R0 40 (1.6”) 25 (55.1) 834 (32.8) - - ------1(2)** (2)** (4)*** (4)***
DP105D40R0 40 (1.6”) 35 (77.2) 1015 (40) - - ------11(2)** 2 2
DP125D40R0 40 (1.6”) 45 (99.2) 1022 (40.2) - - ------111 2 2
DP165D40R0 40 (1.6”) 45 (99.2) 1636 (64.4) - - -------11 2 2
DP205D40R0 40 (1.6”) 45 (99.2) 2025 (79.7) - - -------1(2)** 2 2
Tab. 11.e
1 = the humidifi er is connected to just one distributor
(2) = the humidifi er is connected to two distributors (using the “Y” kit: UEKY000000)
2 = the humidifi er is fi tted with two outlets and can be connected to two linear distributors
(4) = the humidifi er is fi tted with two outlets and can be connected to up to four linear distributors (using two “Y” kits)
* = use CAREL “Y” kit code UEKY000000 (40 mm/1.6” inlet and 2 x 30 mm/1.2” outlets)
** = use CAREL “Y” kit code UEKY40X400 (40 mm/1.6” inlet and 2 x 40 mm/1.6” outlets)
*** = use two CAREL “Y” kit code UEKY40X400 (40 mm/1.6” inlet and 2 x 40 mm/1.6” outlets)
For typical installations of the linear distributors, see Fig. 11.f on page40.