Refrigerant piping 
Connection
Step 2: Remove burrs
Burrs can affect the air-tight seal of 
refrigerant piping connection. They must be 
completely removed.
1.  Hold the pipe at a downward angle to 
prevent burrs from falling into the pipe.
2.  Using a reamer or deburring tool, 
remove all burrs from the cut section of 
the pipe.
Pipe
Reamer
Point down
Step 3: Flare pipe ends
Proper aring is essential to achieve an 
airtight seal.
1.  After removing burrs from cut pipe, 
seal the ends with PVC tape to prevent 
foreign materials from entering the pipe.
2.  Sheath the pipe with insulating material.
3.  Place are nuts on both ends of pipe. 
Make sure they are facing in the right 
direction, because you can’t put them on 
or change their direction after aring.
Flare nut
Copper pipe
4.  Remove PVC tape from ends of pipe 
when ready to perform aring work.
5.  Clamp are form on the end of the pipe. 
The end of the pipe must extend beyond 
the edge of the are form in accordance 
with the dimensions shown in the table 
below.
PIPING EXTENSION BEYOND FLARE 
FORM
Outer Diameter 
of Pipe (mm)
A (mm)
Min. Max.
ø6.35 (ø0.25”) 0.7 (0.0275”)
1.3 (0.05”)
ø9.52 (ø0.375”) 1.0 (0.04”) 1.6 (0.063”)
ø12.7 (ø0.5”) 1.0 (0.04”) 1.8 (0.07”)
ø16 (ø0.63”) 2.0 (0.078”) 2.2 (0.086”)
ø19 (ø0.75”) 2.0 (0.078”) 2.4 (0.094”)
A
Flare form
Pipe
6.  Place aring tool onto the form.
7.  Turn the handle of the aring tool 
clockwise until the pipe is fully ared.
8.  Remove the aring tool and are form, 
then inspect the end of the pipe for 
cracks and even aring.
Step 4: Connect pipes
When connecting refrigerant pipes, be 
careful not to use excessive torque or to 
deform the piping in any way. You should 
rst connect the low-pressure pipe, then the 
high-pressure pipe.
MINIMUM BEND RADIUS
When bending connective refrigerant piping, 
the minimum bending radius is 10cm.
Radius
≥10cm (4in)
Instructions for Connecting Piping to 
Indoor Unit
1.  Align the center of the two pipes that you 
will connect.
Indoor unit tubing Flare nut Pipe
 Page 16-GB