Nov-21 Page 54 of 132 59812-K001 Rev 10
Figure 48 Clear Peak and Average Values
Select YES and press 
2. Clear the maximum average reading for each engine to ensure all test readings are erased.
This can be done via MAIN MENU: ENGINEER 1. Configure System 7. Clr Max Average.
Figure 49 Clear Maximum Average Values
Select the required engine and press 
Figure 50 Confirm Clear Maximum Average Values
Select YES and press 
The above should be carried out for all engines being monitored. This should also be carried out after
any smoke testing.
2.8.6 Average Alarm
1. Enter the Main Menu: Engineer, Figure 41, and select 2. System Status.
Figure 51 System Status Menu
2. Select 1. Engine