Figure 52 Engine Status Selection
3. Select the required Engine (1 2, 3, 4, etc) from the list.
Figure 53 Engine Status
4. Read Maximum actual level value (retain this value for deviation alarm setting).
5. Set Average alarm level to twice the Maximum actual level, as follows:
Return to the Configuration menu, Figure 42 select 3, Alarm Levels,
Figure 54 Set Alarm Levels
Select 1. Set Average Alarm.
Figure 55 Set Engine Average Alarm
Select engine number, press Enter the new alarm level in the range 0.3 to 1.3mg/l as
calculated from above. If the calculated value is outside these limits set the alarm level to
the nearest value in the range.
6. Repeat steps 1 to 5 for all engines.