The status screen shows: 
Average alarm level  The Average Alarm Level set for that engine. 
Maximum actual level  Shows the highest average oil mist level recorded on that engine since the 
maximum level was reset. 
Current Level  The current highest oil mist level indicated by a detector on that engine. 
Slow down relay isolated Yes  indicates the Slowdown / Shutdown relay for that engine is isolated. 
Engine Isolated  Yes indicates all of the detectors on that engine are isolated. 
General fault  Yes indicates there is a fault associated with that engine. 
Number of detectors  Shows the number of detectors configured for that engine 
3.5  TEST MENU 
Although the Control Panel and detectors perform continuous automatic checks a suit of tests are 
provided to allow manual testing of the system functionality to be performed. 
To access the Test Menu, press the Test button 
 
Figure 82  Test Menu   User Level 
3.5.1  Alarm Relay   
Allows the Common Alarm Relay to be tested. 
1.  Select 1. Alarm Relay. 
 
Figure 83  Alarm Relay Test 
2.  Select Enable or Disable to change the relay state and ensure that the  correct engine 
response is initiated by the AMS.