Nov-21 Page 67 of 132 59812-K001 Rev 10
The status screen shows:
Average alarm level The Average Alarm Level set for that engine.
Maximum actual level Shows the highest average oil mist level recorded on that engine since the
maximum level was reset.
Current Level The current highest oil mist level indicated by a detector on that engine.
Slow down relay isolated Yes indicates the Slowdown / Shutdown relay for that engine is isolated.
Engine Isolated Yes indicates all of the detectors on that engine are isolated.
General fault Yes indicates there is a fault associated with that engine.
Number of detectors Shows the number of detectors configured for that engine
3.5 TEST MENU
Although the Control Panel and detectors perform continuous automatic checks a suit of tests are
provided to allow manual testing of the system functionality to be performed.
To access the Test Menu, press the Test button
Figure 82 Test Menu User Level
3.5.1 Alarm Relay
Allows the Common Alarm Relay to be tested.
1. Select 1. Alarm Relay.
Figure 83 Alarm Relay Test
2. Select Enable or Disable to change the relay state and ensure that the correct engine
response is initiated by the AMS.