Following acceptance of the alarm the buzzer will silence and the common alarm relay is deactivated. 
Pressing reset will clear the alarm and return the Control Panel to the normal state. 
 
3.12  BACKUP ALARM 
The  Backup  Alarm  is  a  hard-wired  link  from  each  Detector  installed  on  the system  and  operates 
independent of the system software. This facility will allow any Detector which sees an oil mist level of 
1.6mg/l  up Alarm. This will result in the operation of the buzzer, Alarm LED 
and Common Alarm Relay at the Control Panel. The backup alarm relay in the Junction Box will also be 
activated; the Backup Alarm will also override any Detector or Detectors that are isolated. 
Whilst any Detectors are in a Backup Alarm condition the Accept key is inoperative until the oil 
mist level drops below 1.6mg/l. 
It is possible for a healthy Detector to produce a Backup alarm if the level of oil rises very rapidly. 
NOTE - The Backup Alarm will not operate the Slowdown/Shutdown Relay 
3.13  RELAY OPERATION 
Communication  of alarm and fault conditions  between the OMD  Mk6 
Management System (AMS) is via a series of volt free contact relays. Individual relays are provided for 
Slowdown/Shutdown Alarm, one per engine, Common Alarm and Fault. For each output connections are 
provided to the relay common, normally open and normally closed contacts providing the flexibility to 
meet the interface requirements of the AMS. 
The actions of the relays are detailed below: 
The  Fault  Relay  is  normally  activated  and  de-
activated  when  a  fault  occurs  on  the  Control 
Panel or Detectors. 
In the event power is lost to the Control Panel the 
relay is de-activated ensuring a fault is indicated 
to the AMS.