Nov-21 Page 61 of 132 59812-K001 Rev 10
Figure 70 Smoke Test
3. Dip the wick into the bottle of smoke oil and reseal the bottle firmly.
Only a small quantity of oil is required.
4. Ignite the wick of the smoke tester and blow out the flame. Squeeze the pipette bulb to keep
the wick smoking.
Care to be taken with this activity at all times.
5. While the wick is still smouldering, insert it into the pipe connector and squeeze the pipette
bulb.
6. Observe the wick is still smouldering, insert nylon pipe into the pipe connector of the
Detector and squeeze the pipette bulb.
7. After tests are completed the maximum actual average level, Detector peak level and
current average readings should be erased.
a. From the Configuration menu, Figure 42, select 7. Clr Max Average
Figure 71 Clear Max Average Levels Engine Selection
b. Select the required engine from the list.