Figure 70  Smoke Test 
 
3.  Dip the wick into the bottle of smoke oil and reseal the bottle firmly. 
Only a small quantity of oil is required. 
4.  Ignite the wick of the smoke tester and blow out the flame. Squeeze the pipette bulb to keep 
the wick smoking. 
Care to be taken with this activity at all times. 
5.  While the wick is still smouldering, insert it into the pipe connector and squeeze the pipette 
bulb. 
6.  Observe the  wick  is still  smouldering, insert  nylon pipe into  the pipe connector  of the 
Detector and squeeze the pipette bulb. 
7.  After  tests are  completed  the maximum  actual  average level,  Detector peak  level  and 
current average readings should be erased.  
a.  From the Configuration menu, Figure 42, select 7. Clr Max Average 
 
Figure 71  Clear Max Average Levels   Engine Selection 
b.  Select the required engine from the list.