Nov-21 Page 77 of 132 59812-K001 Rev 10
Detector See section 3.7
Status Allows the panel Configuration to be reset to the default state.
3.10.1 Erase Configuration
Select 3. Status
Figure 110 Erase Configuration
Select 1. Erase Configuration
Figure 111 Confirm Configuration Reset.
Confirm the configuration is to be erased. The panel configuration will revert to the factory default.
Default Configuration
Engines 1
Detectors 4
Average Alarm 0.7mg/l
Deviation Alarm 0.3mg/l
3.11 ALARM OPERATION
3.11.1 Action on Alarm
On receipt of either a Deviation or Average alarm the engine should, unless connected to a Slowdown /
Shutdown relay, be stopped if safe to do so and allowed to cool down so that the background oil mist
levels reduce before entering the engine room. Investigations can then be carried out to identify and
rectify the cause of the alarm. Once the fault in the engine has been rectified the OMD system can be re-
set and the display returns to the normal mode.