Figure 88 Alarm Test Engine Selection
Select the required engine from the list.
Figure 89 Alarm Test Engine
Select the required detector from the list. The Control Panel and Detector will indicate an alarm condition
on the selected detector. The Common Alarm Relay will be operated but not the Shutdown / Slowdown
Relay.
The alarm condition is cleared by pressing the Acknowledge and Reset keys. The Control Panel display
with return to the Main Screen, Figure 74.
3.5.8 Shutdown Relay
Selecting the Test Menu, 4. Test, from Main Menu: Engineer, Figure 41, provides an additional test
option to those obtained at the user level, allowing the operation of the Shutdown / Slowdown Relay to
be tested.
Figure 90 Test Menu Engineer Level
1. Select 8. Shutdown relay.
Figure 91 Shutdown / Slowdown Relay Test Engine Selection
2. Select the engine to be tested from the list.