Detector No fault indication.
Control Panel Activation of the Fault Relay
Buzzer on
Fault LED flashing
System Fault LED flashing
Fault indicated on the LCD
Further details on the type of fault indicated can be obtained by examining the event-log, see section 3.6
5.1.3 Accepted Faults
To silence the Control Panel buzzer press the ACCEPT key. The LCD screen will return to the main screen
but will show a fault has occurred, as shown below.
Figure 131 Example Accepted Fault Screen
The fault text can be displayed by pressing the left arrow key.
Figure 132 Accepted Events Screen
Press the enter key to display the fault text.
Figure 133 Event Text
Use the up and down arrows to scroll through the event text if there is more than one event indicated.
Use the cancel key to return to the main screen.
Pressing the reset key will clear the fault indication and return the system to normal. If the fault has not
been rectified it will be displayed again.