   When a power failure occurs in the system, the frequency converter keeps the motor in power generation
state to maintain the bus voltage at FE.16, preventing the frequency converter from shutting down due to short
-term input voltage cutoff resulting in undervoltage fault.
Bus Voltage
100% Rated Bus Voltage
Output
frequency Hz
Time
Time
Instantaneous power failure
voltage recovery to judge the
time
Instantaneous power failure
pause to judge the voltage
Instantaneous power failure
active to judge the voltage
Figure 8-12-1 Schematic diagram of instantaneous stop and non-stop action
FE.13
Instantaneous power failure
action selection
0 0 ~ 2
FE.14
Instantaneous operation pause
judgment voltage
90.0%
(80.0 ~ 100.0)%
100% is the standard bus voltage
FE.15
Instantaneous power failure
voltage recovery judgment time
0.50s
(0.00100.00)s
-
FE.16
Instantaneous power failure
action judgment voltage
80.0%
(60.0 ~ 100.0)%
100% is the standard bus voltage
0: invalid
1: slow down
2: Deceleration to stop
function
code
name
default
value
Predetermined
area
Parameter Description
   In deceleration mode: when the power grid is restored, the output frequency of the inverter will return
to the target frequency according to the acceleration time;
   In deceleration stop mode: When the power grid is restored, the inverter will continue to decelerate to
0Hz to stop, and the inverter will not start until the inverter sends a start command again.
8.13 Jogging operation
   In some applications, it is necessary for the inverter to run at a low speed for a short time, which is
convenient for testing the condition of the equipment. At this time, jogging operation is used. During jogging
operation, the starting mode is fixed as direct start mode F1.00=0, and the stop mode is fixed as deceleration
stop mode F1.05=0.
   The "MF" key on the operation panel can be used to control the jogging operation (F7.02=0), and the digital
input terminal (X) can also be used to realize related functions.
3: forward jogging
4: reverse jogging
function code
name
default value
Predetermined area
Parameter Description
F5.01
X1 terminal function
1
0 ~ 63
F5.02
X2 terminal function
2
F5.03
X3 terminal function
9
F5.04
X4 terminal function
12
F5.05
X5 terminal function
0
F5.05
X6 terminal function
0
F8.00
Jog running frequency
5.00Hz
0.10F0.07
-
F8.01
jogging acceleration time
20.0s
(0.0 ~ 6500.0) s
-
F8.02
jogging deceleration time
20.0s
(0.0 ~ 6500.0) s
-
061
NVF2G-S Series Inverter User's Guide