----- Supply network analyzer CVMk and CVMk-ITF  ------   Page  Nº  35
 ; The DELAY set value is applied either to the connection or the disconnection
when the alarm conditions occur.
 ; The programming units for the different parameters are:
Parameter Format Example
Voltage Without decimals = V     (xxxx)
With decimals = kV        (xxx.x)
0220   =  220 V
125.0  = 125 kV
25.30   = 25.30 kV
Current A 0150  =  150 A
Powers kW, kvar, kVA 0.540   =   540 W
250.5   =  250.5 kW
Energies kW.h, kvar.h
Power factor x.xx - 0.7  = - 0.70
Frequency xx.x 50.0  = 50 Hz
2   Connections of the module DB-9 connector  :  CVM-ERC-2 ( 2 relays )
Terminals Signal Terminals Signal
RELAY 1
6 Common relay 1
RELAY 2
9 Common relay 2
2N.O. 5N.O.
1N.C. 4N.C.
  - Maximum voltage between terminals = 100 V a.c.
  -  For  the  CVM-ERC-1 and CVM-ERC420-1 modules connect according to the
specified for the RELAY 1.
  ** For the CVM-RED-C2 module ( Communication + 2 static outputs ) see its
corresponding annex.