185
Instruction Manual
SVGm
ENGLISH
8.2.2.2.- Mains Measurements
Table 36: Modbus memory map: Measurements in the Mains.
Parameter L1 L2 L3 LN Units
Current in Mains 9A - 9B 9C - 9D 9E - 9F A0 - A1 [Low] + [Hi] A with 1 decimal
Active power in Mains BF - C0 C1 - C2 C3 - C4 - kW with 2 decimal places and sign.
Reactive power in Mains C5 - C6 C7 - C8 C9 - CA - kVar with 2 decimal places and sign.
Apparent power in Mains CB - CC CD - CE CF - D0 - kVA with 2 decimal places and sign.
cos ɸ in Mains D4 D5 D6 - With 3 decimal
Mains frequency D7 - Hz with 1 decimal
8.2.2.3.- Other parameters of the SVGm static generator
Table 37: Modbus memory map: Static generator parameters (Table 1).
Parameter Address Units
Temperature IGBT 1
(3)
DB ºC with 1 decimal
Temperature IGBT 2
(3)
DC ºC with 1 decimal
Temperature IGBT 3
(3)
DD ºC with 1 decimal
Temperature Inductor 1
(3)
E7 ºC with 1 decimal
Temperature Inductor 2
(3)
E8 ºC with 1 decimal
Temperature IGBT 4
(3) (4)
F5 ºC with 1 decimal
Temperature IGBT 5
(3) (4)
F6 ºC with 1 decimal
Temperature IGBT 6
(3) (4)
F7 ºC with 1 decimal
Temperature Inductor 3
(3) (4)
FB ºC with 1 decimal
Temperature Inductor 4
(3) (4)
FC ºC with 1 decimal
Phase L1 - L2 voltage DE V with 1 decimal
Phase L2 - L3 voltage DF V with 1 decimal
Phase L3 - L1 voltage E0 V with 1 decimal
Positive DC bus voltage E1 V with 1 decimal
Negative DC bus voltage E2 V with 1 decimal
(3)
For a system with devices in parallel, the parameter value is that of the device connected with RS-485.
(4)
Parameters only accessible for the 60 kvar model.
Table 38: Modbus memory map: Static generator parameters (Table 2).
Parameter L1 L2 L3 LN Units
Current in the static generator A3 - A2 A5 - A4 A7 - A6 A9 - A8 [Hi] + [Low] A with 1 decimal
Phase – neutral voltage AA AB AC - V with 1 decimal
% of static generator power used D8 D9 DA - %
Table 39:Modbus memory map: Static generator parameters (Table 3).
Parameter Address Description
SVGm serial no.
(5)
2710 - 2711 Hi [10] + Low [11] serial no.
DSP software version 10C -
HMI software version 1C3 -
(5)
For a system with devices in parallel, the parameter value is that of the device connected with RS-485.