186
SVGm
Instruction Manual
ENGLISH
8.2.2.4.- SVGm messages
Table 40: Modbus memory map: Static generator messages (Table 1).
Parameter Address Status
Device status
(6)
110
1: Start
0: Stop
(6)
For a system with devices in parallel, the parameter value is that of the device connected with RS-485.
Table 41: Modbus memory map: Static generator messages (Table 2).
Parameter Address
Alarm messages 105 (Hi value), 106 (Low value)
Bit Description
0x00000000 There are no alarms
0x00000001 DC Bus voltage error
0x00000002 L1 overcurrent alarm
0x00000004 L2 overcurrent alarm
0x00000008 L3 overcurrent alarm
0x00000010 L1 overvoltage alarm
0x00000020 L2 overvoltage alarm
0x00000040 L3 overvoltage alarm
0x00000080 DC+ bus overvoltage alarm
0x00000100 DC- bus overvoltage alarm
0x00000200 IGBT failure
0x00000400 IGBT failure
0x00000800 IGBT failure
0x00001000 IGBT failure
0x00004000 High temperature IGBT
0x00008000 High temperature inductor
0x00010000 Initial Conditions Error
0x00040000 Hardware failure
0x00080000 DC Bus charge failure
0x00100000 Selt-test failed
0x00200000 Temperature alarm
0x01000000 DSP failure
0x02000000 5V supply failure
Table 42: Modbus memory map: SVGm messages (Table 3).
Parameter Address
HMI alarm messages 44F
Bit Description
0x0001 Internal communications alarm.