187
Instruction Manual
SVGm
ENGLISH
Table 43: Modbus memory map: Static generator messages (Table 3).
Parameter Address
Initial Conditions for which the device
does not start up.
(7)
108
Bit Description
0x0001 Discharging DC bus
0x0002 Minimum Mains Voltage
0x0004 Minimum temperature value
0x0008 Frequency error
0x0010 Charging DC bus
0x0020 Minimum DC bus voltage
0x0040 DC Bus imbalance
0x0080 The device does not communicate
0x0200 Minimum load current
0x0400 Maximum load current
0x0800 THDv > 40%
(8)
0x1000 Mains voltage limits: High
(8)
0x4000 CAN Comms loss
0x8000 SVGm cannot generate the expected current waveform.
(7)
For a system with devices in parallel, the parameter value is that of the device connected with RS-485.
(8)
Warning messages available with software versions DSP ≥ 1.61 and HDMI ≥ 1.2006.
Table 44: Modbus memory map: Static generator messages (Table 4).
Parameter Address
SVGm status
(9)
104
Status (Decimal value) Description
0 The device is starting the systems.
50 Initiating internal communication systems
60 Configuring the device.
100 The SVGm is starting up.
200 Waiting for the conditions to be met in order to operate.
300 Device stopped.
400 The SVGm is synchronising with the mains.
500 Charging process of the internal bus prior to start-up.
600 Device is operating.
700 An alarm has been generated.
(9)
For a system with devices in parallel, the parameter value is that of the device connected with RS-485.

Table of Contents